Capacitance split phase compensating thrown-and-cut unit
 
Product overview£º
IDL-F series Capacitance split phase compensating thrown-and-cut unit is a kind of relatively advanced thrown-and-cut unit. Approved by Quality Inspecting and Testing Center for Reactive Compensation Integrated Equipment of State Ministry of Power Industry on Jul.12th, 2003, it is in compliance with the relevant requirement of Q/32028i\IDCZ02¨C2003 Standard filed with State Standard Measurement Bureau.
It is usually necessary to carry out power compensation to the circuit due to the inductance components in the illumination circuit.
In the past, AC contactor was usually used as switching element. Nevertheless, there will be a heavy current flowing past the contact of AC contactor at the moment when the AC contactor is switched in the circuit just on a voltage peak value because the switching action occurs so frequently and the voltages at the two ends of capacitor are unable to change abruptly, so that the heavy current makes the contact terminals melt, vaporize and ablate and gradually damages the contacts. In case that SCR is used alone as switching element, the requirement for the SCR is relatively high because the illumination circuit is operating permanently under the conditions of high voltage and heavy current. Meanwhile, the switching of SCR will import the crossover distortion from the power supply to the circuit, which only increases harmonics. Therefore we now make the cubicle switch integrated the contact with the SCR component and use it as the switching element of capacitance compensating controlled circuit, the thrown-and-cut unit. Thus it will make the capacitance compensating switching unit more reliable as we bring the advantages of these two electric components into play and overcome their disadvantages.
Product model£º
 
Service condition£º Diagram of capacitance split phase compensating thrown-and-cut unit
1¡¢Not exceeding an altitude of 2,500 m
2¡¢Environment temperature: -20¡æ~55¡æ
3¡¢Air humidity: not exceeding 90% at 40¡æ
4¡¢No corrosive gas, electric dust or inflammables and explosives in the operation environment.
5¡¢Voltage variation range: 160V ¡« 250V
 
Operation process of capacitance compensating digital controlled thrown-and-cut unit
1¡¢When the capacitor is switching in:
Receiving the voltage signal outputted by the compensation controller, the chip-microcomputer begins testing the operation of the circuit and sends out the turn-on control signal for SCR. The SCR is turned on when the voltage is crossing zero and the red indicator (4) turns on. Then the capacitor switches in and sends out operation signal for the contactor or relay after a time lag of 0.5-1s; the contactor or relay operates and green indicator (3) turns on. The SCR is cut off,the red indicators (4) turns off and the unit begins its normal operation.
2¡¢When the capacitor is cut off:
Receiving the zero signal outputted by the compensation controller, the chip-microcomputer detects the blackout of controlling signal and sends out the turn-on signal for the SCR. At this point, the voltages at the two ends of the SCR become zero, then the red indicator (4) turns on. After a time delay of 0.5-1s, the cut off signal for the contactor or relay is sent out and the contactor or relay is cut off. After another time lag of 0.5-1s, the SCR crosses zero and cuts off, then the capacitor cuts off and both indicators turns off. The circuit resumes its initial condition.
The controlling method succeeds in averting the current surge to the mechanical moving contacts because the SCR turns on and cuts off and the capacitor switches in and cuts off all under zero voltage condition, so that the moving contacts can operate with long lives. Meanwhile, the SCR only works at the moment when the capacitor throws and cuts, its operation time being very short. As a matter of fact, this design brings the advantages of these two electrical components into full play. ¡¡
The Company adopts the module structure for the inner cubicle switch of capacitance compensating digital controlled thrown-and-cut unit, so that the protection properties of the product are better. In addition, the damage occurred in the site can be solved simply by replacing the relevant module, which greatly contributes to easy and fast maintenance.
The capacitance compensating digital controlled thrown-and-cut unit falls into 2 categories: split compensating unit and 3-phase compensating unit. As to the 3-phase compensating unit, only one phase is processed for signal sampling while 3 phases are processed for compensation and cutting-off at the same time, which is suitable for the applications of relatively balanced 3-phase load such as motor and so on.
As to split phase compensating unit, each phase will be processed for testing and compensation, so that the circuit of each phase can acquire the optimum compensation, which is suitable for street lamp illumination circuit.
The Company attaches great importance to the technology innovation and dedicates itself to the quality improvement of its products.
Concerning the key components and heavy duty control elements, we all adopt imported materials and leave sufficient overmeasure in the design and selection of materials, so that the product is ensured to operate effectively for long term.
 
Diagram for external dimension and installing size of capacitance compensating digital controlled thrown-and-cut unit (IDL-F-IV-25A-220V)A£º
Note: (1) Incoming line of major loop (Power off) (2) Outgoing line of major loop (load Capacitor) (3) Green indicator (Showing the thrown-and-cut of compensating capacity) (4) Red indicator (Showing the thrown-and-cut of SCR) (5) Controlling signal leg of circuit (6) Controlling signal zero conductor (7) Mounting hole

©2004 Ideal Electrical Equipment Technology Co., Ltd. All rights reserved. Powered & Designed by changenet.cn